Gree GMV5 Series Service Manual page 93

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

LED1
Function
Display
Code
Mode
A6
On
A6
On
A6
On
A6
On
On the master unit, press "SW6" to return to the upper level (press "SW6" in setting status to return to
the upper level; press "SW6" after settings are completed to restore the normal operating status of the
unit).
If no button operations are performed on the master unit for five minutes, the function setting
automatically quits and the unit restores the current status.
The default factory setting is ―nA‖ cooling/heating.
 A2 Refrigerant recovery operation settings
Step 1: Confirm entering the A2 refrigerant recovery operation settings. The master unit is displayed as
follows:
Function
Code
A2
Step 2: The default setting is ―01‖. Select "01" or "02" by pressing "SW1 (UP)" or "SW2 (DOWN)". Press
"SW7" to confirm selecting the mode.
On the master unit, press "SW6" to return to the upper level.
If no button operations are performed on the master unit for five minutes, the function setting
automatically quits and the unit restores the current status.
Indoor unit refrigerant recovery
Step 3: Select "01‖ as in step 2 to enter IDU refrigerant recovery. Digital LEDs and status LEDs of all
basic modules are displayed as follows:
LED1
Function
Display
Code
Mode
A2
On
LED3 shows the low-pressure value of a module. If the value is negative, LED3 circularly displays the
negative code "nE‖ and the numeric value every one second. For example, for -30C, LED3 alternately
displays ―nE‖ for one second and then ―30‖ for another second.
Step 4: Close liquid-tube stop valves of all basic modules of the ODU. When the low-pressure value
displayed on LED3 continually blinks, quickly close air-tube stop valves of all basic modules and then
press "SW7" on the master unit to confirm completing refrigerant recovery or power off the entire unit.
If no operations are performed after the low-pressure value displayed on LED3 continually blinks for
three minutes, the entire unit will be forcibly stopped.
On the master unit, press "SW6" to return to the upper level for restoring the standby status of the entire
unit (press "SW6" in setting status to return to the upper level; press "SW6" after settings are completed
to restore the normal operating status of the unit).
Note:
Another startup is not allowed within 10 minutes after refrigerant recovery.
Basic module refrigerant recovery
Step 3: Set the basic module requiring refrigerant recovery to module emergency operation status and
close the liquid-tube stop valve of the emergency status module. Select "02‖ as in step 2 to enter basic
module refrigerant recovery. The display is as follows:
Function
Code
A2
LED3 shows the high-pressure value of the module.
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
LED2
ODU Function Mode
Code
nC
nH
nA
nF
LED1
Refrigerant
Display
Recovery
Mode
Code
On
01
LED2
Refrigerant
Recovery Code
01
LED1
Display
Current
Mode
Progress
On
02
Display
ODU Function Mode
Mode
On
On
On
On
LED2
Display
Current
Mode
Status
Blinking
Display
Mode
On
[Module low-pressure Ps]
LED2
Display
Current
Mode
Status
Module
On
high-pressure
90
LED3
Code
nC
nH
nA
nF
LED3
Display
Mode
00
Blinking
LED3
Current Status
LED3
Display
Mode
On
Display
Mode
On
On
On
On
Display
Mode
On