GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
opened
as
required.
The
system's
exhaust
pressure
rises and
the low
pressure
is too low
2. The
(compar
system
ed with
pipeline
the
is
referenc
blocked.
e value).
——
3. The
ambient
temperat
ure is
too low.
——
4. The
pressure
sensor
is faulty.
Touch the
pipe along
the flowing
direction of
refrigerant to
2.1. The
feel the
system
temperature
air
difference.
pipeline
The
is
difference is
blocked.
large.
Touch the
pipe along
the flowing
direction of
refrigerant to
feel the
temperature
difference.
The
2.2 The
difference is
fluid
large or part
pipe is
of the pipe is
blocked.
frosting.
Touch the
pipe along
the flowing
direction of
refrigerant to
feel the
temperature
2.4 The
difference.
pipe that
The
connect
difference is
s the
large or part
IDU is
of the pipe is
blocked.
frosting.
3.1 The
outdoor
ambient
temperat
ure is
lower
than
-25° C
in
Measure the
the
outdoor
heating
ambient
mode.
temperature.
Stop the
whole
4.1 The
system. Test
low
the system's
pressure
balance
sensor
pressure 20
is faulty.
minutes
147
2.1.1 The
block is
caused by
solder.
2.1.2 The
Cut off
pipeline is
the pipe
blocked by
and
impurities.
check it.
——
——
2.4.1 The
block is
caused by
solder.
2.4.2 The
Cut off
pipeline is
the pipe
blocked by
and
impurities.
check it.
——
——
——
——
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
It is a
normal
phenome
non
caused
by the
protectio
n
function.
Replace
the high
pressure
sensor.