Gree GMV5 Series Service Manual page 145

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

2.2 Pressure exception
Primary reason
Fau
lt
cod
Descripti
e
Fault
on
1. The
stop
valve of
the ODU
is not
fully
opened
as
required.
High
pressur
e
E1
protecti
on
2. The
system
pipeline
is
blocked.
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Possible reasons
Secondary reason
Confirmat
ion
Descripti
method
on
——
——
2.1. The
system
air
pipeline
is
blocked.
2.2 The
fluid pipe
is
blocked.
The
system's
exhaust
pressure
rises and
the low
pressure
2.4 The
is too low
pipe that
(compare
connects
d with the
the IDU
reference
is
value).
blocked.
Confirmation
Descripti
method
——
——
2.1.1
The
block is
caused
Touch the
by
pipe along
solder.
the flowing
direction of
2.1.2
refrigerant to
The
feel the
pipeline
temperature
is
difference.
blocked
The
by
difference is
impuritie
large.
s.
Touch the
pipe along
the flowing
direction of
refrigerant to
feel the
temperature
difference.
The
difference is
large or part
of the pipe is
——
frosting.
2.4.1
The
Touch the
pipe along
block is
the flowing
caused
by
direction of
solder.
refrigerant to
feel the
2.4.2
temperature
The
difference.
pipeline
The
is
difference is
blocked
large or part
by
of the pipe is
impuritie
frosting.
s.
142
Tertiary reason
Confirmat
ion
on
method
Fully open
Manual
the stop
check
valve.
Replace
and solder
the pipe.
Cut off
the pipe
Replace
and
and solder
check it.
the pipe.
Replace
and solder
——
the pipe.
Replace
and solder
the pipe.
Cut off
the pipe
Replace
and
and solder
check it.
the pipe.
Solution