Gree GMV5 Series Service Manual page 114

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

If the displayed quantity is inconsistent with the number of actually connected modules, check whether
communication cables are correctly connected between modules in power-off status. Then perform
commissioning again.
Note: It is very important to correctly confirm the number of ODUs. If the confirmed quantity is
inconsistent with the actual quantity, the system may improperly run.
Step 8: When the unit runs to step 04, users need to manually confirm the number of indoor modules.
The main board of each module is displayed as follows:
Progress
04_Indoor unit
quantity
confirmation
If the displayed quantity is consistent with the number of actually connected modules, press "SW7" on
the master unit to confirm. The main board is displayed as follows and the unit automatically enters the
next commissioning step.
Progress
04_Indoor unit
quantity
confirmation
Note: It is very important to correctly confirm the number of IDUs. If the confirmed quantity is
inconsistent with the actual quantity, the system may improperly run.
Step 9: Unit commissioning step 05 is internal communication detection.
If no exception is detected, the main board is displayed as follows and the unit automatically enters the
next commissioning step.
Commissioning Code
Progress
Code
05_Internal
communication
detection
db
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Corresponding faults include:
Commissioning Code
Progress
Code
db
05_Internal
communication
detection
db
db
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Commissioning
Code
LED1
Display
Code
Status
db
On
Commissioning
Code
LED1
Display
Code
Status
db
On
Progress Code
LED1
Display
Status
Code
On
05
Progress Code
LED1
Display
Status
Code
On
05
On
05
On
05
Progress Code
LED2
Display
Code
Status
04
On
Progress Code
LED2
Display
Code
Status
04
On
Status Code
LED2
LED3
Display
Status
Code
On
OC
Status Code
LED2
LED3
Display
Status
Code
On
C2
On
C3
On
CH
111
Status Code
LED3
Display
Code
Status
Number of
connected
IDUs
Blinking
Status Code
LED3
Display
Code
Status
OC
On
Display
Status
Meaning
The system
completes detection
and automatically
On
enters the next step.
Display
Status
Meaning
The system detects
communication failure
between master unit
and inverter
On
compressor driver.
The system detects
communication failure
between master unit
and inverter fan
On
driver.
The rated capacity
ratio is over-high
On
between indoor and