Gree GMV5 Series Service Manual page 153

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

Feedback
from user
Exception
A. When
the IDU is
working in
the
cooling
mode and
the
electronic
expansio
n valve is
opened to
2000PLS,
the
exhaust
temperatu
re of the
IDU's coil
is more
than
5° C
higher
than the
intake
temperatu
Poor
re; B.
heating/co
when the
oling
IDU is
performan
working in
ce
the
heating
mode and
the
electronic
expansio
n valve is
opened to
2PLS, the
intake
temperatu
re of the
IDU's coil
is more
than
12° C
lower
than the
saturation
temperatu
re
correspon
ding to
the high
pressure;
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Primary reason
Confirm
Descript
ation
ion
method
1. The
stop
valve of
the
ODU is
——
not fully
opened
as
required
.
——
2. The
system
pipeline
is
blocked.
Possible reasons
Secondary reason
Confirm
Descripti
ation
on
method
——
——
Touch
the pipe
along
the
flowing
direction
of
refrigera
nt to feel
the
temperat
2.1. The
ure
system
differenc
air
e. The
pipeline
differenc
is
e is
blocked.
large.
Touch
the pipe
along
the
flowing
direction
of
refrigera
nt to feel
the
temperat
ure
differenc
e. The
differenc
e is large
2.2 The
or part of
fluid pipe
the pipe
is
is
blocked.
frosting.
2.4 The
Touch
pipe that
the pipe
connects
along
the IDU
the
is
flowing
blocked.
direction
150
Tertiary reason
Confirm
Descrip
ation
tion
method
——
Manual
check
2.1.1
The
block is
caused
by
solder.
2.1.2
The
pipeline
is
blocked
Cut off
by
the pipe
impuriti
and
es.
check it.
——
——
2.4.1
The
block is
Cut off
caused
the pipe
by
and
solder.
check it.
Solution
Fully
open the
stop
valve.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.
Replace
and
solder
the pipe.