Open all valves in
order that the
vacuum pump
extracts air through
all the valves
Oil checking
valve
Low pressure
check valve
Step 15: Fill refrigerant.
Before filling refrigerant, check its manufacturer, package, and print information. Besides, check
refrigerant pressure and quality against the saturation pressure / temperature list.
1. Measure and check the pressure of the entire refrigerant product against the saturation pressure /
temperature list. Verify temperature parameter. If the difference between the actual temperature and the
parameter value is 3° C or more, the refrige rant quality is unsatisfactory.