Electrical Parameters of High-static-pressure Air-duct-type Air Conditioner
Model
GMV-ND56PHS/A-T
GMV-ND63PHS/A-T
GMV-ND71PHS/A-T
GMV-ND80PHS/A-T
GMV-ND90PHS/A-T
GMV-ND100PHS/A-T
GMV-ND112PHS/A-T
GMV-ND125PHS/A-T
GMV-ND140PHS/A-T
GMV-ND160PHS/A-T
GMV-ND224PH/A-T
GMV-ND280PH/A-T
Note:
(1) The circuit breaker and power cable specifications are selected based on the maximum power
(maximum current) of the units.
(2) The power cable specifications are obtained under the conditions that the ambient temperature is
40℃, the working temperature of multi-core copper cable (for example, YJV cable) is 90℃, and the
cable is exposed in cable troughs. In different applications, adjust the specifications based on national
standards.
(3) Only copper conductor cable can be used.
(4) The sectional area of a wire is applicable for a distance range of up to 15 m. If the distance is greater
than 15 m, increase the sectional area of the wire correspondingly to prevent the wire from being burned
due to overload current and to avoid fire.
(5) The circuit breaker specifications are obtained under the conditions that the ambient temperature is
40℃ when the circuit breaker is working. In different applications, adjust the specifications based on the
circuit breaker manual.
(6) The circuit breaker must support magnetic release and thermal release at the same time to protect
the system from short circuit and overload.
Electrical Parameters of Fresh Air Conditioning IDU
Mode
GMV-NX140P/A(X1.2)-K
GMV-NX224P/A(X2.0)-M
GMV-NX280P/A(X2.5)-M
GMV-NX280P/A(X3.0)-M
GMV-NX450P/A(X4.0)-M
Notes:
(1) . The circuit breaker and power cable specifications in the above table are selected according to the
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Power Supply
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
220-240V~50Hz/208-230V~60Hz
Power Supply
Specification
220-240V~50Hz
380-415V~50Hz
380-415V~50Hz
380-415V~50Hz
380-415V~50Hz
Circuit Breaker Capacity
(A)
6
6
6
6
6
6
6
6
6
6
10
10
Minimum Sectional
Circuit Breaker
Area of Grounding
Capacity/A
6
6
6
6
10
11
Minimum Sectional Area
(mm² ) of Grounding Wire
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Minimum Sectional
Area of Power
2
Wire/mm
Cable/mm
1.0
1.0
1.0
1.0
1.0
2
1.0
1.0
1.0
1.0
1.0

Hide quick links: