DC Current
Range
Resolution
60.00A
0.01A
600.0A
0.1A
1000A
1A
AC TRMS Current / INRUSH current
Range
Resolution
60.00A
0.01A
600.0A
0.1A
1000A
1A
(*) Accuracy specified from 10% to 100% of the measuring range, Input impedance: > 9M , sinusoidal waveform
Response time INRUSH function: 100ms
DC Current by means of standard clamp transducers
Output
Range
ratio
1000mA
1000mV/1000mA
10A
100mV/1A
40A (**)
10mV/1A
100A
10mV/1A
400A (**)
1mV/1A
1000A
1mV/1A
(*) Accuracy referred to the sole instrument without transducer; (**) with clamp transducer HT4006
For a non-sinusoidal waveform, accuracy is: (10.0%rgd + 10digits)
AC TRMS, AC+DC TRMS Current with standard clamp transducers
Output
Range
ratio
1000mA
1V/1mA
10A
100mV/1A
40A (**)
10mV/1A
100A
10mV/1A
400A (**)
1mV/1A
1000A
1mV/1A
(*) Accuracy referred to the sole instrument without transducer; (**) with clamp transducer HT4006
AC TRMS Current with flexible clamp transducer (F3000U)
Output
Range
ratio
30A
100mV/1A
300A
10mV/1A
1mV/1A
3000A
(*) Accuracy referred to the sole instrument without transducer ; Accuracy specified from 5% to 100% of the measuring range
Accuracy of PEAK function: ±(10%reading+20dgt), Response time of PEAK function: 1ms
Diode test
Function
Accuracy
(2.0%reading + 8digits)
Accuracy (*) (50Hz 60Hz)
(2.5%reading + 5digits)
Resolution
1mA
0.01A
0.01A
0.1A
0.1A
1A
Resolution
(50Hz 60Hz)
1mA
(0.8%rdg+5dgt)
0.01A
0.01A
(1.8%rdg+5dgt)
0.1A
(0.8%rdg+5dgt)
0.1A
(1.8%rdg+5dgt)
1A
(0.8%rdg+5dgt)
Resolution
Accuracy (50Hz 400Hz) (*)
0.01A
0.1A
1A
Test current
<1.5mA
EN - 42
Overload protection
Overload protection
Accuracy (*)
(0.8%reading + 5digits)
(1.8%reading + 5digits)
(0.8%reading + 5digits)
(1.8%reading + 5digits)
(0.8%reading + 5digits)
Accuracy (*)
(61Hz 1kHz)
(2.4%rdg+5dgt)
(3.0%reading + 5digits)
Max voltage with open circuit
ECLIPSE - HT9025
1000VDC/ACrms
1000VDC/ACrms
Overload protection
1000VDC/ACrms
Overload
protection
1000VDC/ACrms
Overload
protection
1000VDC/ACrms
3.3VDC
Need help?
Do you have a question about the ECLIPSE HT9025 and is the answer not in the manual?
Questions and answers