Fire Alarm; Emergency Unlocking; Tamper Message/Fault Message; Message - Assa Abloy ePED 1386-00 Installation And Fitting Instructions

Escape route technology door terminal
Table of Contents

Advertisement

ye
gn
gn
ye
ye
gn
gn
ye

Fire alarm

and/or Emergency
unlocking
rd ye
rd
ye
ye
rd
ye
rd
Tamper alarm has
Locked status
rd
rd
rd
rd
Intrusion alarm
system is active
EN
18
Fire alarm
In the case of a fire alarm, the Hi-O Technology™ components are actuated by a
fire alarm system. The escape route locking systems are automatically unlocked
and retain this status until actuation by the fire alarm system is lifted again.
If the actuation by the fire alarm system is lifted again, the components lock again
if no further release commands are issued.
Other Hi-O Technology™ locking systems respond according to their respective
configuration.

Emergency unlocking

If the Emergency Open push-button is pressed, an Emergency unlocking or re-
lease request is issued to the central control. If an Emergency unlock has been
triggered with an Emergency Open push-button, the Emergency Open push-
button must be unlocked manually, wherein the system is also reset to normal
operation.

Tamper message/fault message

The following statuses trigger a tamper message for a locked door:
· The door is open and/or
· the escape route locking system is unlocked.
The door remains in Locked status.
The tamper status can be reset centrally or at the door.

Message

Intrusion alarm system activated

If a block command is issued by an intrusion alarm system, lock commands are
transmitted to all Hi-O Technology™ component and all control devices are
deactivated.
The escape door can only be opened after the Emergency Open push-button has
been pressed.
The following commands are exceptions and can still be activated:
· Resetting of Emergency unlock,
· Activation of escape route locking systems ("Active and inactive escape route
securing system," page 17).
Functions

Hide quick links:

Advertisement

Table of Contents
loading