Set-Up Operation - Assa Abloy ePED 1386-00 Installation And Fitting Instructions

Escape route technology door terminal
Table of Contents

Advertisement

!
A

Set-up operation

Set-up operation
Warning!
Danger due to faulty commissioning: In order to ensure the safety of the
product, commissioning must be performed by a qualified person. ASSA ABLOY
Sicherheitstechnik GmbH offers training for qualification in the requisite skills.
Safety requirements during commissioning include:
· The owner has received a confirmation of approval for use from the inspection
authorities.
· Conformity of the products with the approval according to EltVTR
(Tab. 5, page 56 "Appendix," page 60)
· Assembly according to the installation manual
· Testing of the unimpeded opening and closing function of the doors with the
escape route securing system deactivated
· Bolting of the doors after activation of the escape route securing system
· Allows the doors to be opened after actuation of the Emergency Open
push-button(s)
· The function must be tested with connected to fire alarm system
· The commissioning must be documented. ASSA ABLOY Sicherheitstechnik GmbH
offers a test log book for this purpose.
Attention!
Propy damage from connection with USB devices: The connection jacks on the
external display module 1386D00-DISP and on the Emergency Open module 1386D00
are not USB jacks and are only intended for connection of these two devices via a
standard USB cable A/B.
EN
53