UC600 Rotary Swtiches and LEDs

Setting Addresses Using Rotary Switches

There are three rotary switches on the front of the Tracer UC600 for the purpose of defining a
three-digit address when it is installed on a BACnet communications network. The three-digit
address setting is used as both the rotary switch value and the BACnet device ID.
For Trane BACnet MS/TP systems, the rotary switch value must be between 1 and 127. Although
"0,0,0," is a valid BACnet address, Trane reserves this address for the Tracer SC controller. For
non-Trane systems, see . All device addresses on the BACnet MS/TP link must be unique.
Figure 1. Setting rotary switch values on UC600
I I m m p p o o r r t t a a n n t t : : Each Tracer UC600 device on the BACnet link must have a unique rotary switch value,
Use a 1/8 in. (3 mm) flathead screwdriver
to set rotary switches. Switches rotate
in either direction.

Location of LEDs

Light emitting diodes (LEDs) indicate the operation and communication status of the controller.
For detailed information about wiring communication links, refer to the BACnet Best Practices
and Troubleshooting Guide (BAS-SVX51).
6
Before powering up Tracer UC600, set the rotary switch value as shown in the following
figure.
If the Tracer UC600 was previously powered up, do the following if you wish to make
changes:
Make the preferred changes to the rotary switch value as illustrated in .
Power down the Tracer UC600; when re-powered the new rotary switch value should be
active.
For controllers that are connected through BACnet/IP, or wireless via ZigBee™, valid unit
controller rotary switch values can range from 001 to 999.
N N o o t t e e : : Valid rotary switch values used with the Tracer UC600 are 001 to 120 for BACnet MS/TP.
Rotary switches after
addresses have been set
ADDRESS
x100
x10
x1
otherwise communication problems will occur.
IM C
24
24
24
VAC
VAC
VAC
XFMR
OUT
MBUS
OUT
UI 1
UI 2
UI 3
UI 4
UI 5
1
U C 600
B O 1
B O 2
B O 3
B O 4
ADDRESS
x100
x10
x1
AO1
AO 2
AO 3
AO 4
AO 5
AO 6
UI 9
UI 10
UI 11
UI 12
UI 13
UI 14
+ 24
+ 24
VDC
VDC
OUT
LINK
UI 6
UI 7
UI 8
RELAYS 0 . 5 A MAX
BO 1
BO 2
BO 3
BO 4
BAS-SVP042A-EN
IM C
+ 24
VDC
IMC
P 1
LINK
MBUS
IM C
TX
RX
LINK
SERVI C E
ACT
SERVICE TOOL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents