Trane Tracer UC600 Installation Manual page 41

For modular self contained
Table of Contents

Advertisement

Table 9. All Object Types Sorted by Object Name (continued)
Object
Object Name
Identifi-
er
Diagnostic:
Compressor 4 Low
BV294
Superheat
Diagnostic:
BV295
Compressor 4 Safety
Circuit Alarm
Diagnostic:
Compressor 4 Suction
BV296
Pressure Sensor
Failure
Diagnostic:
Compressor 4 Suction
BV297
Temperature Sensor
Failure
Diagnostic: Condenser
BV322
Water Flow Loss
Diagnostic: Dirty Air
BV72
Filter
Diagnostic: Dirty
BV320
Condenser Tee Filter
Diagnostic: Discharge
BV19
Air Low Temperature
Lockout
Diagnostic: Discharge
BV42
Air Temperature
Source Failure
Diagnostic: Duct
BV15
Static Pressure Failure
Diagnostic: Software
BV321
High Duct Static Alarm
Diagnostic: Space
BV11
Temperature Source
Failure
Dirty Air Filter DP
AV129
Setpoint
Discharge Air Cooling
AV24
Setpoint BAS
Discharge Air Cooling
AV18
Setpoint Max BAS
BAS-SVP042A-EN
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
Pressure
-10.0 to 5.0 in
in(H2O)
(H2O)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
10°C (50°F) to
(°C or °F)
29.4°C (85°F)
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
When the Object
Exists
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Water Cooled
Condenser Units
Non latching Diagnostic, clears
Only
All Units
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Water Cooled
Condenser Units
Latching Diagnostic. Cleared with
Only
Filter Alarm Reset or Power Cycle.
All Units
Latching Diagnostic. Cleared with
Alarm Reset or Power Cycle.
All Units
Non latching Diagnostic, clears
Units with Duct
Non latching Diagnostic, clears
Pressure Sensor
All Units
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Units with Space
Temperature Option.
Non latching Diagnostic, clears
Filter pressure which will generate a
dirty filter alarm when the filter
All Units
differential pressure exceeds it.
User Entered Setpoint to control the
All Units
Discharge Air to when in the cooling
Sets the maximum Reset Temperature
Units with Discharge
when in the cooling mode.
Air Reset Method.
Description
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Writeable
automatically
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
automatically
Open = Normal
Closed = Failure
Read Only
automatically
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Writeable
automatically
Read Only
Read Only
mode.
Read Only
Read/
Write
41