O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 7. Binary Values (continued)
Object
Object Name
Identifi-
er
Water Side
BV255
Economizer Lockout
BAS
Diagnostic:
Compressor 1
BV260
Discharge Pressure
Sensor Failure
Diagnostic:
BV261
Compressor 1 Frostat
Diagnostic:
BV262
Compressor 1 High
Pressure Shutdown
Diagnostic:
Compressor 1 High
BV263
Superheat
Diagnostic:
Compressor 1 Low
BV264
Superheat
Diagnostic:
BV265
Compressor 1 Safety
Circuit Alarm
Diagnostic:
Compressor 1 Suction
BV266
Pressure Sensor
Failure
Diagnostic:
Compressor 1 Suction
BV267
Temperature Sensor
Failure
Diagnostic:
Compressor 2
BV270
Discharge Pressure
Sensor Failure
Diagnostic:
BV271
Compressor 2 Frostat
Diagnostic:
BV272
Compressor 2 High
Pressure Shutdown
Diagnostic:
Compressor 2 High
BV273
Superheat
Diagnostic:
Compressor 2 Low
BV274
Superheat
Diagnostic:
BV275
Compressor 2 Safety
Circuit Alarm
Diagnostic:
Compressor 2 Suction
BV276
Pressure Sensor
Failure
Diagnostic:
Compressor 2 Suction
BV277
Temperature Sensor
Failure
Diagnostic:
Compressor 3
BV280
Discharge Pressure
Sensor Failure
26
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
When the Object
Exists
Units with Water
Side Economizer
Closed = Locked Out
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Description
Open = Available
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
BAS-SVP042A-EN
Read/
Write