Multi-State Values - Trane Tracer UC600 Installation Manual

For modular self contained
Table of Contents

Advertisement

Table 7. Binary Values (continued)
Object
Object Name
Identifi-
er
Warning: Compressor
2 High Discharge
BV371
Press Warning
Warning: Compressor
BV375
3 Frostat Warning
Warning: Compressor
3 High Discharge
BV376
Press Warning
Warning: Compressor
BV380
4 Frostat Warning
Warning: Compressor
4 High Discharge
BV381
Press Warning
Table 8. Multi-state Values
Object
Object Name
Identifi-
er
Occupancy Request
MV1
Occupancy Status
MV2
Heat Cool Mode
MV3
Request
MV4
Heat Cool Mode Status
Emergency Override
MV8
BAS
MJC MSC Factory
MV39
Program Version
BAS-SVP042A-EN
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
None
None
None
None
Units of
Minimum
Maximum
Measure
None
None
None
None
None
None
None
None
None
None
None
None
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
When the Object
Exists
Units with at least 2
Compressor
Closed = Warning Active
Units with at least 3
Compressor
Closed = Warning Active
Units with at least 3
Compressor
Closed = Warning Active
Units with at least 4
Compressor
Closed = Warning Active
Units with at least 4
Compressor
Closed = Warning Active
When the Object
Exists
[3, Occupied Bypass]
All Units
[4, Occupied Standby]
[3, Occupied Bypass]
All Units
[4, Occupied Standby]
[3, Morning Warm-up]
All Units
[9, Emergency Heat]
[13, Maximum Heat]
[3, Morning Warm-up]
All Units
[9, Emergency Heat]
[13, Maximum Heat]
All Units
All Units
Description
Open = Normal
Read Only
Open = Normal
Read Only
Open = Normal
Read Only
Open = Normal
Read Only
Open = Normal
Read Only
Description
[1, Occupied]
[2, Unoccupied]
[5, Auto]
[1, Occupied]
[2, Unoccupied]
Read Only
[5, Auto]
[1, Auto]
[2, Heat]
[4, Cool]
[5, Night Purge]
[6, Pre Cool]
[7, Off]
[8, Test]
[10, Fan Only]
[11, Free Cool]
[12, Ice-Making]
[14, Economizer]
[15, Dehumidify]
[16, Calibrate]
[1, Auto]
[2, Heat]
[4, Cool]
[5, Night Purge]
[6, Pre Cool]
[7, Off]
[8, Test]
Read Only
[10, Fan Only]
[11, Free Cool]
[12, Ice-Making]
[14, Economizer]
[15, Dehumidify]
[16, Calibrate]
[1, Normal]
[2, Pressurize]
[3, Depressurize]
[4, Purge]
[5, Shutdown]
[6, Fire]
Read Only
Version 1.4
Read/
Write
Read/
Write
Writeable
Writeable
Writeable
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents