Trane Tracer UC600 Installation Manual page 35

For modular self contained
Table of Contents

Advertisement

Table 9. All Object Types Sorted by Object Name (continued)
Object
Object Name
Identifi-
er
Compressor 2 Suction
AI97
Pressure Sensor
Compressor 2 Suction
AI98
Temperature
Compressor 3
Calculated Diff
AV333
Refrigerant Pressure
Compressor 3
Calculated Saturated
AV334
Discharge Temp
Compressor 3
Calculated Saturated
AV335
Suction Temp
Compressor 3
BV210
Calculated Status
Compressor 3
AV336
Calculated Superheat
Compressor 3 Call
BV211
Compressor 3
BO13
Command
Compressor 3 Cond
BV213
Purge Status
Compressor 3 Cond
BV214
Valve Open
Compressor 3
AO83
Condenser Regulating
Valve
Compressor 3
AI99
Discharge Pressure
Sensor
Compressor 3
Estimated Cond
AV337
Approach Temp
Compressor 3
Estimated Evap
AV338
Approach Temp
Compressor 3 Failure
BV215
Reset
Compressor 3 High
BI92
Pressure Cutout
Compressor 3 Lockout
BV31
BAS
Compressor 3 Max
AV339
Cond Valve Setpoint
Compressor 3 Min
AV340
Cond Valve Setpoint
BAS-SVP042A-EN
Units of
Minimum
Measure
Maximum
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
-500 psi to 500
PSI
psi
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
None
None
None
None
None
None
0% to 100%
Percent
Open
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
None
None
None
None
Percent
-150% to 150%
Percent
-150% to 150%
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
When the Object
Exists
Units with at least 2
Local Compressor Refrigerant Suction
Compressors
(Low) Pressure Sensor
Units with at least 2
Local Compressor Refrigerant Suction
Compressors
(Low) Temperature Sensor
Calculated Differential Pressure
Units with 3
between the Discharge and Suction
Compressor
Calculated Saturated Discharge
Units with 3
Temperature calcualted by the
Compressor
refrigerant temp and pressure.
Units with 3
Calculated Suction Temperature by
Compressor
pressure to temperature conversion.
Units with 1
Compressor
Calculated Superheat of the Suction
Units with 3
line by Temperautre and pressure
Compressor
Units with 1
Compressor
Normally Open Contacts Used Only
Units with at least 3
Open = Stop Closed = Run
Compressors
Normally Closed Contacts not used
Units with 1
Compressor
Closed = Purge Active
Units with 1
Compressor
Unit that Circuit 3
Analog Control that regulates water
has a Water
throught the water cooled condenser
Regulating Valve
installed
Units with at least 3
Local Compressor Refrigerant
Compressors
Discharge (High) Pressure Sensor
Units with 3
Calculated Condenser approach
Compressor with
temperature based off Refrigerant PT
Cond Reg Valve
Conversion and water temperature.
Calculated approach temperuatre of
Units with 3
the Evaporator refrigerant temprature
Compressor
and the air temperature.
Units with 1
Compressor
Normally Closed Input
Units with at least 3
Compressors
Units with at least 3
Compressors
Closed = Locked Out
Units with 3
Maximum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
Units with 3
Maximum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
Description
Pressure Sensors
Open = Off
Closed = On
sensors.
Open = Stop
Closed = Run
Open = Inactive
Open = Closed
Closed = Open
of the compressor
Open = Normal
Closed = Reset
Open = Alarm
Closed = Normal
Open = Available
Read/
Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Writeable
35