Trane Tracer UC600 Installation Manual page 50

For modular self contained
Table of Contents

Advertisement

A A l l a a r r m m i i n n g g
Table 10. Alarm Objects (continued)
Object Identifier
50
Object Name
Diagnostic:
Compressor 3 Low
BV284
Superheat
Diagnostic:
BV285
Compressor 3 Safety
Circuit Alarm
Diagnostic:
Compressor 3 Suction
BV286
Pressure Sensor
Failure
Diagnostic:
Compressor 3 Suction
BV287
Temperature Sensor
Failure
Diagnostic:
Compressor 4
BV290
Discharge Pressure
Sensor Failure
Diagnostic:
BV291
Compressor 4 Frostat
Diagnostic:
BV292
Compressor 4 High
Pressure Shutdown
Diagnostic:
Compressor 4 High
BV293
Superheat
Diagnostic:
Compressor 4 Low
BV294
Superheat
Diagnostic:
BV295
Compressor 4 Safety
Circuit Alarm
Diagnostic:
Compressor 4 Suction
BV296
Pressure Sensor
Failure
Diagnostic:
Compressor 4 Suction
BV297
Temperature Sensor
Failure
Diagnostic: Dirty
BV320
Condenser Tee Filter
Diagnostic: Software
BV321
High Duct Static Alarm
Diagnostic: Condenser
BV322
Water Flow Loss
Local Auto Stop
BV329
Supply Fan 1 Failure
BV331
Description
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Notification Class
0
1
1
1
1
1
1
0
0
1
1
1
2
1
1
1
1
BAS-SVP042A-EN