Trane Tracer UC600 Installation Manual page 40

For modular self contained
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 9. All Object Types Sorted by Object Name (continued)
Object
Object Name
Identifi-
er
Diagnostic:
Compressor 2 Suction
BV277
Temperature Sensor
Failure
Diagnostic:
Compressor 3
BV280
Discharge Pressure
Sensor Failure
Diagnostic:
BV281
Compressor 3 Frostat
Diagnostic:
BV282
Compressor 3 High
Pressure Shutdown
Diagnostic:
Compressor 3 High
BV283
Superheat
Diagnostic:
Compressor 3 Low
BV284
Superheat
Diagnostic:
BV285
Compressor 3 Safety
Circuit Alarm
Diagnostic:
Compressor 3 Suction
BV286
Pressure Sensor
Failure
Diagnostic:
Compressor 3 Suction
BV287
Temperature Sensor
Failure
Diagnostic:
Compressor 4
BV290
Discharge Pressure
Sensor Failure
Diagnostic:
BV291
Compressor 4 Frostat
Diagnostic:
BV292
Compressor 4 High
Pressure Shutdown
Diagnostic:
Compressor 4 High
BV293
Superheat
40
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
When the Object
Exists
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Description
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Writeable
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
BAS-SVP042A-EN
Read/
Write

Hide quick links:

Advertisement

Table of Contents
loading