Alarming; Alarm Objects - Trane Tracer UC600 Installation Manual

For modular self contained
Table of Contents

Advertisement

Alarming

The UC600 unit for modular self contained units has several objects used for communicating
alarms to the system.
Table 10. Alarm Objects
Object Identifier
48
Object Name
Emergency Stop
BI9
External Auto Stop
BI10
Input Status
Supply Fan 1 VFD
BI80
Fault
Supply Fan 2 VFD
BI81
Fault
Supply Fan 3 VFD
BI82
Fault
Supply Fan 4 VFD
BI83
Fault
Supply Fan 5 VFD
BI84
Fault
Supply Fan 6 VFD
BI85
Fault
Compressor 1 High
BI90
Pressure Cutout
Compressor 2 High
BI91
Pressure Cutout
Compressor 3 High
BI92
Pressure Cutout
Compressor 4 High
BI93
Pressure Cutout
Compressor 1 VFD
BI98
Fault
Diagnostic: Duct
BV15
Static Pressure Failure
Diagnostic: Discharge
BV19
Air Low Temperature
Lockout
Diagnostic: Discharge
BV42
Air Temperature
Source Failure
Diagnostic: Dirty Air
BV72
Filter
Active CoolCoil Control
BV76
Sensor Failed
Diagnostic:
Compressor 1
BV260
Discharge Pressure
Sensor Failure
Diagnostic:
BV261
Compressor 1 Frostat
Description
Normally Closed Input
Open = Emergency Stop
Closed = Normal
Normally Closed Input
Open = External Stop
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Normally Closed Input
Open = Alarm
Closed = Auto
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Alarm Reset or Power Cycle.
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Notification Class
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
BAS-SVP042A-EN