Trane Tracer UC600 Installation Manual page 49

For modular self contained
Table of Contents

Advertisement

Table 10. Alarm Objects (continued)
Object Identifier
BAS-SVP042A-EN
Object Name
Diagnostic:
BV262
Compressor 1 High
Pressure Shutdown
Diagnostic:
Compressor 1 High
BV263
Superheat
Diagnostic:
Compressor 1 Low
BV264
Superheat
Diagnostic:
BV265
Compressor 1 Safety
Circuit Alarm
Diagnostic:
Compressor 1 Suction
BV266
Pressure Sensor
Failure
Diagnostic:
Compressor 1 Suction
BV267
Temperature Sensor
Failure
Diagnostic:
Compressor 2
BV270
Discharge Pressure
Sensor Failure
Diagnostic:
BV271
Compressor 2 Frostat
Diagnostic:
BV272
Compressor 2 High
Pressure Shutdown
Diagnostic:
Compressor 2 High
BV273
Superheat
Diagnostic:
Compressor 2 Low
BV274
Superheat
Diagnostic:
BV275
Compressor 2 Safety
Circuit Alarm
Diagnostic:
Compressor 2 Suction
BV276
Pressure Sensor
Failure
Diagnostic:
Compressor 2 Suction
BV277
Temperature Sensor
Failure
Diagnostic:
Compressor 3
BV280
Discharge Pressure
Sensor Failure
Diagnostic:
BV281
Compressor 3 Frostat
Diagnostic:
BV282
Compressor 3 High
Pressure Shutdown
Diagnostic:
Compressor 3 High
BV283
Superheat
Description
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
A A l l a a r r m m i i n n g g
Notification Class
1
1
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
0
49