O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 4. Analog Values (continued)
Object
Object Name
Identifi-
er
Compressor 4 Max
AV353
Cond Valve Setpoint
Compressor 4 Min
AV354
Cond Valve Setpoint
Compressor 4 Run
AV355
Hours
Compressor 4
AV356
Sequence Number
Compressors Available
AV361
Condenser Control
AV363
Percent of Design
Condenser Design
AV364
Max Pressure
Condenser Purge Time
AV365
(Min)
Condenser Control
AV366
Pressure Setpoint
Condenser Tee
AV368
Strainer Calculated
Diff Press
Condenser Tee
Strainer Calculated
AV369
High Pressure
Condenser Tee
AV370
Strainer Calculated
Low Pressure
Condenser Tee
Strainer Diff Pressure
AV371
Alarm Setpt
Condenser Tee
AV372
Strainer High Pressure
Offset
Condenser Tee
AV373
Strainer Low Pressure
Offset
Condenser Valve
AV375
Control P Gain
Duct Static Pressure
Safety Lockout
AV378
Setpoint
Variable Speed
Compressor Ramp Up
AV380
Delay (Sec)
Water Side Econ
Calculated Enable
AV382
Setpoint
Water Side Econ
AV383
Sample Time (Min)
Water Side Econ Valve
AV384
Control P Gain
Water Side
AV385
Economizer Enable
Offset
22
Units of
Minimum
Measure
Maximum
Percent
-150% to 150%
Percent
-150% to 150%
0 -
None
9999999827968
None
0 - 5
None
-1000 to 1000
Percent
50 % to 100 %
-500 psi to 500
PSI
psi
None
5 to 60
-500 psi to 500
PSI
psi
-10 psi to 10 psi
PSI
-10 psi to 600 psi
PSI
-10 psi to 600 psi
PSI
-500 psi to 500
PSI
psi
-15 psi to 15 psi
PSI
-15 psi to 15 psi
PSI
None
0.1 to 10
-5.0 to 5.0 in
in(H2O)
(H2O)
None
30 to 250
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
1 to 5
None
-1000 to 1000
▲ Temperature
4 - 7 Degrees
When the Object
Exists
Units with 4
Maximum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
Units with 4
Minimum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
Totalized run hours of the compressor
Units with 4
from the last run hour reset or
Compressor
Units with 4
Sequence Number to indicate what
Compressor
sequence the compressor will start in.
Number of Compressor which are
All Units
sets the percentage of the Control
Water Cooled
Pressure Setpoint that will be used to
Condenser Units
control the Discharge Pressure on the
Only
Water Cooled
Condenser Max Design Pressure set by
Condenser Units
Only
Water Cooled
Time that the Compressor regulating
Condenser Units
valves will be open during purge mode
Only
Calculated Condenser Control
Water Cooled
Pressure Setpoint based on the
Condenser Units
Percentage of Design and the Max
Only
Water Cooled
Calculated Differential Pressure
Condenser Units
between the High and Low Condenser
Only
Tee Strainer sensors.
Water Cooled
Calculated High Pressure based off
Condenser Units
High Pressure input and High Pressure
Only
Water Cooled
Calculated Low Pressure based off Low
Condenser Units
Pressure input and Low Pressure
Only
Water Cooled
Alarm Setpoint to generate alarm for a
Condenser Units
dirty strainer Tee based on the
Only
differential pressure.
Water Cooled
Offset applied to the High Pressure
Condenser Units
reading to calibrate the sensor with a
Only
Water Cooled
Offset applied to the Low Pressure
Condenser Units
reading to calibrate the sensor with a
Only
P Gain for the PID Condenser
All Units
If the Duct Static exceeds this
Setpoint it will shut down the unit and
All Units
require a manual reset.
This delay time disabled the Speed
Units with variable
PID calculation from calculating until
speed compressor
the delay time expires, due to the
(s)
automatic ramp up built into the VFD
Temperature that the entering water
Units with Water
must be in order to enable the Water
Side Economizer
side economizer for cooling.
time that the Water Side Economizer
Units with Water
will sample the water to see if it can
Side Economizer
Units with Water
P Gain for the PID Condenser
Side Economizer
This is used to calculate the Water
Units with Water
Side Econ Enable Setpoint
Side Economizer
Description
Read Only
program change.
Read Only
Read Only
available to run.
unit
Read Only
the Factory.
Read Only
Pressure
Read Only
Read Only
Offset
Read Only
Offset
local gauge.
local gauge.
Read Only
Calculation
Writeable
Read Only
Read Only
Writeable
use for cooling.
Read Only
Calculation
Writeable
BAS-SVP042A-EN
Read/
Write
Writeable
Writeable
Writeable
Writeable
Writeable
Writeable
Writeable