Trane Tracer UC600 Installation Manual page 27

For modular self contained
Table of Contents

Advertisement

Table 7. Binary Values (continued)
Object
Object Name
Identifi-
er
Diagnostic:
BV281
Compressor 3 Frostat
Diagnostic:
BV282
Compressor 3 High
Pressure Shutdown
Diagnostic:
Compressor 3 High
BV283
Superheat
Diagnostic:
Compressor 3 Low
BV284
Superheat
Diagnostic:
BV285
Compressor 3 Safety
Circuit Alarm
Diagnostic:
Compressor 3 Suction
BV286
Pressure Sensor
Failure
Diagnostic:
Compressor 3 Suction
BV287
Temperature Sensor
Failure
Diagnostic:
Compressor 4
BV290
Discharge Pressure
Sensor Failure
Diagnostic:
BV291
Compressor 4 Frostat
Diagnostic:
BV292
Compressor 4 High
Pressure Shutdown
Diagnostic:
Compressor 4 High
BV293
Superheat
Diagnostic:
Compressor 4 Low
BV294
Superheat
Diagnostic:
BV295
Compressor 4 Safety
Circuit Alarm
Diagnostic:
Compressor 4 Suction
BV296
Pressure Sensor
Failure
Diagnostic:
Compressor 4 Suction
BV297
Temperature Sensor
Failure
Diagnostic: Dirty
BV320
Condenser Tee Filter
Diagnostic: Software
BV321
High Duct Static Alarm
Diagnostic: Condenser
BV322
Water Flow Loss
BV325
Filter Alarm Reset
BAS-SVP042A-EN
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
When the Object
Exists
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Latching Diagnostic. Cleared with
Compressor
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Units with 1
Compressor
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Water Cooled
Condenser Units
Latching Diagnostic. Cleared with
Only
Filter Alarm Reset or Power Cycle.
All Units
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Water Cooled
Condenser Units
Non latching Diagnostic, clears
Only
All Units
Description
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
Open = Normal
Closed = Failure
Read Only
automatically
Open = Normal
Writeable
Closed = Reset
Read/
Write
27