Trane Tracer UC600 Installation Manual page 37

For modular self contained
Table of Contents

Advertisement

Table 9. All Object Types Sorted by Object Name (continued)
Object
Object Name
Identifi-
er
Compressor 4 Failure
BV225
Reset
Compressor 4 High
BI93
Pressure Cutout
Compressor 4 Lockout
BV32
BAS
Compressor 4 Max
AV353
Cond Valve Setpoint
Compressor 4 Min
AV354
Cond Valve Setpoint
Compressor 4 Mode
MV73
Compressor 4 Run
BV226
Hour Reset
Compressor 4 Run
AV355
Hours
Compressor 4 Safety
BI109
Circuit Status
Compressor 4 Safety
BV227
Lockout
Compressor 4
AV356
Sequence Number
Compressor 4 Suction
AI103
Pressure Sensor
Compressor 4 Suction
AI104
Temperature
Compressor Cond
BV250
Valve Installed
Compressor Error
AV176
Deadband
Compressor P Gain
AV173
Compressor Speed P
AV174
Gain
Compressors Available
AV361
Condenser Control
AV363
Percent of Design
Condenser Control
AV366
Pressure Setpoint
Condenser Design
AV364
Max Pressure
BAS-SVP042A-EN
Units of
Minimum
Measure
Maximum
None
None
None
None
None
None
Percent
-150% to 150%
Percent
-150% to 150%
None
None
None
None
0 -
None
9999999827968
None
None
None
None
None
0 - 5
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
0.5 to 25
None
0.5 to 25
None
-1000 to 1000
Percent
50 % to 100 %
-500 psi to 500
PSI
psi
-500 psi to 500
PSI
psi
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
When the Object
Exists
Units with 1
Compressor
Normally Closed Input
Units with at least 4
Compressors
Units with at least 4
Compressors
Closed = Locked Out
Units with 4
Maximum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
Units with 4
Maximum Valve position for the
Compressor with
condenser regulating valve.
Cond Reg Valve
[4, Diag: Safety Circuit Alarm]
[5, Diag: Low Superheat]
[6, Diag: Suction Press Sensor Failure]
[7, Diag: Suction Temp Sensor
Units with at least 4
[8, Diag: Frostat Aarm]
Compressors
[9, Diag: Discharge Press Sensor
[10, Diag: High Pressure Cutout
[12, Diag: High Superheat]
[13, Warn: High Disc Press]
[14, Comp Locked Out]
[15, Warn: Frostat Warning]
Units with 1
Compressor
Totalized run hours of the compressor
Units with 4
from the last run hour reset or
Compressor
Normally Open Input
Units with at least 4
Compressors
Closed = Circuit Closed (Completed)
Units with 1
Compressor
Closed = Lockout Active
Units with 4
Sequence Number to indicate what
Compressor
sequence the compressor will start in.
Units with at least 4
Local Compressor Refrigerant Suction
Compressors
(Low) Pressure Sensor
Units with at least 4
Local Compressor Refrigerant Suction
Compressors
(Low) Temperature Sensor
Open = Not Installed
All Units
Deadband Compressor calculation
All Units
uses for speed calculation
P Gain for the PID Cooling Calculation
All Units
P Gain for the PID Cooling Calculation
All Units
Number of Compressor which are
All Units
sets the percentage of the Control
Water Cooled
Pressure Setpoint that will be used to
Condenser Units
control the Discharge Pressure on the
Only
Calculated Condenser Control
Water Cooled
Pressure Setpoint based on the
Condenser Units
Percentage of Design and the Max
Only
Water Cooled
Condenser Max Design Pressure set by
Condenser Units
Only
Description
Open = Normal
Closed = Reset
Open = Alarm
Closed = Normal
Open = Available
[1, Off]
[2, Starting]
[3, Running]
Failure]
Failure]
Alarm]
[11, VFD Fault]
Open = Normal
Closed = Reset
program change.
Open = Circuit Open
Open = Inactive
Closed = Installed
available to run.
unit
Pressure
the Factory.
Read/
Write
Read Only
Read Only
Read Only
Writeable
Read Only
Writeable
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Writeable
Read Only
Writeable
Read Only
Read Only
37