Trane Tracer UC600 Installation Manual page 42

For modular self contained
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 9. All Object Types Sorted by Object Name (continued)
Object
Object Name
Identifi-
er
Discharge Air Heating
AV25
Setpoint BAS
Discharge Air Low
AV190
Temperature Cutout
Discharge Air
AV21
Temperature Setpoint
Active
Discharge Air
AV72
Temperature Setpoint
Local
Discharge Air
Temperature Setpoint
AV21
Pgain
Duct Static Pressure
AV72
Active
Duct Static Pressure
AI12
Local
Duct Static Pressure
Safety Lockout
AV378
Setpoint
Duct Static Pressure
AV92
Setpoint Active
Duct Static Pressure
AV91
Setpoint BAS
DX Staging Status
MV42
Emergency Override
MV8
BAS
Emergency Stop
BI9
External Auto Stop
BI10
Input Status
BV62
Fan Latch
BV65
Fan Safeties OK
BV325
Filter Alarm Reset
Fixed Speed
BV326
Compressor Rotate
BAS
Fixed Speed
Compressor Rotate
BV327
Schedule=BAS/Local
Fixed Speed Lead
MV78
Compressor
BV21
Heat Cool Mode Active
42
Units of
Minimum
Measure
Maximum
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
Pressure
-5.0 to 5.0 in
in(H2O)
(H2O)
Pressure
-0.25 to 5.2 in
in(H2O)
(H2O)
-5.0 to 5.0 in
in(H2O)
(H2O)
Pressure
-5.0 to 5.0 in
in(H2O)
(H2O)
Pressure
-0.0 to 5.0 in
in(H2O)
(H2O)
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
When the Object
Exists
User Entered Setpoint to control the
Unit with a Heating
Discharge Air to when in the Heating
Coil
User Entered Setpoint to disable the
unit when the Discharge Air
All Units
Temperature goes below this
Setpoint the unit is using to control the
All Units
discharge air temperature to.
Setpoint the unit is using to control the
Units with Discharge
discharge air temperature to.
Air Reset Method.
Units with Discharge
P Gain for the PID Discharge Air Reset
Air Reset Method.
Duct static pressure the unit is
All Units
controling the fans to.
All Units
Local Duct Static Pressure Sensor.
If the Duct Static exceeds this
Setpoint it will shut down the unit and
All Units
require a manual reset.
Setpoint being used to control the fans Read Only
All Units
User entered Setpoint to control the
All Units
fans to the desired pressure.
[2, Start Interval Active]
All Units
[3, Shutdown Delay Active]
[4, Subtract Suspended]
All Units
Normally Closed Input
All Units
Open = Emergency Stop
Normally Closed Input
All Units
Open = External Stop
All Units
All Units
All Units
Units with more than
2 Compressors
Units with more than
2 Compressors
Units with at least 2
Compressors
All Units
Description
mode.
temperature.
Calculation
[1, Normal]
[1, Normal]
[2, Pressurize]
[3, Depressurize]
[4, Purge]
[5, Shutdown]
[6, Fire]
Closed = Normal
Closed = Auto
Open = Off
Closed = Fan Run
Open = No
Closed = Yes
Open = Normal
Closed = Reset
Open = Normal
Closed = Rotate
Open = BAS
Closed = Local
[1, Not Used]
[2, Compressor 2]
[3, Compressor 3]
[4, Compressor 4]
Open = Heat
Closed = Cool
BAS-SVP042A-EN
Read/
Write
Read Only
Read Only
Writeable
Writeable
Read Only
Read Only
Read Only
Read Only
Writeable
Writeable
Read Only
Read Only
Read Only
Writeable
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only