5. Highlight the channel range menu item
6. Press Edit until the desired channel range is displayed
7. Press Down to highlight the Alarm
8. Press Edit to change the Alarm setting to the desire alarm
9. Replace the PGM Jumper (J2)
10. Press Next twice
11. Press Edit to accept the changes, and reboot the controller
The Channel Range and Alarm LED should now be illuminated next to the desired settings.
If it is desired to have Alarm 1, 2 or 3 be failsafe, this setting can be changed in the Discrete Relay Settings
Menu. To reach this menu, enter the Main Menu, highlight the Alarm Outputs Menu Item and press Edit.
Highlight Discrete Relay, and Press Edit.
Setup of the Discrete Relays is now complete.

4.6.2 Analog 4-20mA and Bridge Input

Each Optional I/O board must be assigned to a channel group (either 1-8 or 9-16). The current channel
group the board is assigned to be is indicated at the top of the option board by a green LED. To change
the assigned channel group perform the following:
1. Enter the Diagnostics Menu
a) Press the Main Menu button
b) Press the Up button to highlight Diagnostics
c) Press Edit three times to enter the Diagnostics Menu
2. Press Up to highlight I/O Board Config
3. Press Edit
4. Remove the PGM Jumper (J2) on the option board you wish to configure
5. Press Edit until the desired channel group is displayed
6. Replace the PGM Jumper (J2)
7. Press Next twice
8. Press Edit to accept the changes, and reboot the controller
The Channel group LED should now be illuminated next to the desired channel group.
UM-1097
Revision B
53