Standard Relay 2 - RC Systems ViewSmart 1600+ Operation Manual

Table of Contents

Advertisement

Standard Relay 2

Type
Chan
nel
A1 Votes
N/A
A2 Votes
N/A
A3 Votes
N/A
Acknowledge
N/A
Failsafe
N/A
Zone
1
N/A
Enable
Zone
2
N/A
Enable
Zone
3
N/A
Enable
Zone
4
N/A
Enable
Zone
5
N/A
Enable
Zone
6
N/A
Enable
Zone
7
N/A
Enable
UM-1097
Revision B
First
Last
Block
Size
40140
40140
N/A
40141
40141
N/A
40142
40142
N/A
40143
40143
N/A
40144
40144
N/A
40145
40145
N/A
40146
40146
N/A
40147
40147
N/A
40148
40148
N/A
40149
40149
N/A
40150
40150
N/A
40151
40151
N/A
Rea
Write
Notes
d FC
FC
3
6, 16
Alarm 1 channels required. 0 - 16
3
6, 16
Alarm 2 channels required. 0 – 16
3
6, 16
Alarm 3 channels required. 0 - 16
3
6, 16
Relay is acknowledgeable. No = 0,
Yes = 1
3
6, 16
Relay is failsafe. No = 0, Yes = 1
3
6, 16
Use zone 1 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 2 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 3 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 4 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 5 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 6 channels for voting. No =
0, Yes = 1
3
6, 16
Use zone 7 channels for voting. No =
0, Yes = 1