2.8.3 Optional Computer Gateway CLI I/O

The optional computer gateway adds one or two connections to a host computer.
1. Remove the rear center-section cover of tower #2 and connect the computer cable
(503790-xxx) to
JA
tighten the screws (2) on the connector.
The tab number (-xxx) in the cable drawing number refers to its length in meters. The
maximum cable length is 305 meters (1000 feet).
I/O CLI
JB
RS-449
Figure 2-16 — CLI I/O Board
2. If the host computer is running in a redundant mode, an additional cable must be
connected from the computer to
screwdriver to tighten the screws (2) on the connector.
3. Using a cable-tie (51190879-001) on each cable, fasten the cables to their strain-relief
clamps (marked
OPTIONS
Enhanced Micro TDC 3000 User's Manual
of the CLI I/O board (see Figure 2-16). Use a small screwdriver to
of the CLI I/O board (see Figure 2-16). Use a small
JB
in Figure 2-7) on the lower transition panel.
2-20
2.8.3
JA
9/95