Current In Amperes At 120 Vac; Unpacking - Honeywell Enhanced Micro TDC 3000 User Manual

8-node
Table of Contents

Advertisement

2.3.3 Current in Amperes at 120 Vac

Twr #1 (1 US, AM, NIM, & drives)
Twr #1 (2 US, AM, NIM, & drives)
Twr #1 (1 US, AM, NIM, CG, & drives) typical
Twr #2 (HM only)
Twr #2 (HM & US)
Twr #2 (HM, US, & US)
Twr #2 (HM, US, & CG)
Monitor, 20 inch CRT
Monitor, 21 inch CRT
ASPI-41 Printer
For Advanced Process Manager power consumption, consult Process Manager /Advanced
Process Manager Planning, part of the System Site Planning - 1 binder.

2.4 UNPACKING

When the equipment arrives at the system site, open each shipping box, remove the
protective wrapping and carefully inspect each piece for any physical damage. If damaged,
immediately notify the carrier and your Honeywell sales representative as to the extent and
type of damage. Also check each piece of equipment against the invoice list for any missing
items.
Optional touchscreens will be factory installed. Be careful not to lift the CRTs by holding the
touchscreen bezel. Due to the weight you may easily damage the touchscreen.
Enhanced Micro TDC 3000 User's Manual
Avg
True RMS
typical
1.65
3.53
typical
1.95
4.12
2.01
4.25
typical
1.15
2.54
typical
1.54
3.34
typical
1.84
3.91
typical
1.95
4.12
typical
0.5
1.14
typical
0.8
1.5
typical
1.1
1.75
CAUTION
2-3
2.3.3
Peak
Wattage
BTUs/hr
10
266
907.06
11.2
319
1087.79
11.4
329
1121.89
6.5
185
630.85
9.5
249
849.09
10.7
299
1019.59
11.2
319
1087.79
3.1
79
269.39
4.1
83
283
9.1
210
716