5.2.2 Loading Network Interface Module and UCN Devices

The Network Interface Module is loaded through the Gateways and Interfaces Status
display, which is called up by selecting GATEWAYS on the System Status display.
1. Select the node number 3 (primary) or 4 (redundant) for the NIM to be loaded.
2. If the AUTOLOAD NET target is present, select AUTOLOAD NET, press ENTER,
and skip to step 4. Otherwise, select MANUAL LOAD. Continue with step 3.
3. Select OPERATOR PROGRAM, and follow the prompters to specify the program
source [normally, you will select the default source (NET = HM)]. Then, select
EXECUTE COMMAND.
4. Wait from a few seconds to a few minutes for the status for the NIM you selected in
step 1 to go to OK.
MAKE SELECTION
UCN CABLE STATUS: OK
01 NIM 02
03 PM 04
OK
OK
BACKUP
BACKUP
LOAD/SAVE
CONTROL
RESTORE
STATES
PROGRAM
RESTORE
LOAD
DATA
When the NIM is loaded and operating (primary NIM status = OK), you can load the APM
program and restore Advanced Process Manager data through the UCN status display.
Refer to subsection 4.4 in this manual.
Enhanced Micro TDC 3000 User's Manual
UCN 10 STATUS
05 PM 06
07 LM 08
ALIVE
OK
ALIVE
BACKUP
AUTO
UCN CABLE
CHECKPT
STATUS
SAVE
LADDER
DATA
LOAD
5-7
24 Feb
15:50:06
UCN CONTROL STATE: BASIC
UCN AUTO CHECKPNT: INHIBIT
NIM AUTO CHECKPNT: DISABLE
RUN
SLOT
STATES
SUMMARY
LADDER
CANCEL
SAVE
5.2.2
1
DETAIL
STATUS
ENTER
53290