Check HM Operation—
10. On the Operator's Keyboard press the SYSTEM STATUS key. On the System
Status display, select the HM Node Object Box, then select the NODE STATUS
target.. If the HM status is anything other than OK, you should not continue until
the problem is fixed. For information on how to use the "Load_HM.EC" file on
&C8, refer to Sections 13 through 17 in the System Startup Guide - Cartridge
Drive, in the Implementation/Startup & Reconfiguration - 1 binder.
If the status is OK, and you want to check the contents of the HM, do the
following—
On the Engineering Main Menu, select COMMAND PROCESSOR.
Key in the command LSV NET. Press ENTER. The resulting output on the
screen should appear similar to Table 4-1. Table 4-1 shows all volumes and
directories on the HM. You may not have them all. For example, &CGO and
&HGO are optional Computer Gateway and Hiway Gateway programs.
4.2.1.2 Network Configuration Completion
At this point the Local Control Network is configured with the prebuilt NCF file. You can
browse through the items on the left column of the Engineering Menu if you like by
selecting the targets one at a time. Some of the configuration displays have several pages.
Use the PAGE FWD and PAGE BACK keys to see all pages. Return to the Engineering
Menu by pressing CTL/HELP after looking over each item. Refer to the subsection 4.2.2
for a listing of the prebuilt NCF file.
Optional EPLCG or CG—
If the system has an optional EPLCG or CG node, you can add either or both to the
network with the On-Line Reconfiguration procedures described in Section 7 of the
Network Data Entry manual. When a EPLCG or CG node is added to the network, it
must be loaded with its Operator Personality. You will want to have these personalities
on the HM, however, they are not preloaded like the others and all HM space is
allocated. Solution: the existing HM volume named PICS is large enough to hold this
software. Create directories for the files you need to load (e.g., &HG0, &HGG, and/or
&CI0). Refer to Section 16 in the System Startup Guide—Cartridges, for loading
procedures and Section 18 to load the Operating personality into the node(s). Note that a
EPLCG is configured as a subset of the Hiway Gateway node.
The next step is to load the Gateways and Modules (subsection 4.3).