9. On the UCN Status display, the target 03 APM should still be selected (filled with
color).
10. Select LOAD/SAVE RESTORE. The box should change to white.
11. Select RESTORE DATA; then select ENTER.
12. On the Restore UCN Node display, select DEFAULT SOURCE, then select
EXECUTE. When RESTORED is displayed, proceed to Step 12.
13. Select DETAIL STATUS. Check the boxes on the Detail Status display. For each
implemented IOP, a box should contain the IOP type (e.g., HLAI) and the word
IDLE.
4.4.2 Expanded Standard APM Cabinet
If you are configuring a double-sided nonredundant cabinet with added IOP cards, use the
procedure in 4.4.1, then reconstitute the entity $NM01B03 (refer to the Data Entity Builder
Manual for the reconstitute procedure). Add the extra I/O Modules to the configuration for
the cabinet. Load the data by pressing F12.
To configure any other APM cabinet, follow the procedures in Task 32 of the System
Startup Guide—Cartridge Drive.
4.4.3 UCN/APM Box Point Configuration Data
The following entity defines the primary Advanced Process Manager Module as node 03 on
process network 01 (the UCN). This checkpoint information was loaded as the Data
Source for the APM. A redundant APM is configured as node 04 but otherwise contains
default values.
Parameter
Description
(Name)
Entity name
NTWKNUM
Network number
NODENUM
Node number
NODETYP
Node type
NODASSN
Node assignment
MOVPVTXT
Moving text descriptor
BADPVTXT
Bad PV text
The following entity defines the physical configuration of the Advanced Process Manager
and several key operational characteristics.
Parameter
Description
(Name)
Entity name
NTWKNUM
Network number
NODENUM
Node number
CTLOPT
Control option
NCTLSLOT Number of control slots
NPVSLOT
Number of PV slots
NLOGSLOT Nmbr. of Logic slots
NDCSLOT
Nmbr. of Digital Comp. slots 150
Enhanced Micro TDC 3000 User's Manual
Value, Primary APM
$NM01N03
01
03
APM
ThisNIM
Neither
Both
Value
Parameter
$NM01B03 NPMSLOT
01
NUMERIC
03
SCANRATE
On
PKGOPT
40
IOMFILEA
20
IOMCARDA
25
IOMTYPE
FAILOPT(n)
4-15
Description
No. of Process Module Slots
No. Numerics in PM Box Pnt.
Scan rate
PMM Packaging Option
IOP file number
IOP card number
IOP card type
Output failure option
4.4.2
Value
30
2047
Reg1Log1
Nonredun
(see chart)
(see chart)
(see chart)
Unpower
9/95