Selecting—In the pages that follow, when instructed to select something on the display, do
so by moving the cursor onto the target and then press the SELECT key on the appropriate
keyboard. If you have the optional touchscreen, touch the target to move the cursor onto
the target; the select is performed by removing your finger from the display. If you have
the optional trackball, position the cursor onto the target with the trackball and press the
select key on the trackball. When instructed to enter something, move the cursor to the
appropriate port, key in (type) the data, and then press the ENTER key on the appropriate
keyboard or on the trackball. In Section 5, use the Operator's keyboard unless otherwise
instructed. On the trackball, the right-hand key is the Select key and the left-hand key is the
Enter key.
5.1.1.1 How to "Bootload" US 1 with the Universal Personality from a
Preloaded HM
The HM has been factory loaded, configured, initialized, with the volumes, directories, and
data defined in Table 4-1, you can apply power and let it "boot" itself up (autoboot). To do
this, after the tower 2 (left tower) power switch has been off for at least several seconds,
turn it on. After several seconds, the three-digit-LED status indicator for the HM should
show the node number "6." (The HM is the node C position, board slots 7 and 8, in tower
2. For more information, refer to Table 6-1.) Wait about five minutes before attempting to
start up the US.
Startup is the only situation where an HM should be forced to autoboot by turning power off and
then back on. After a US is running, you can use the HM Status display (with the ENABLE
LD/DMP status set to ENABLE) to twice SHUT DOWN the HM (for instructions, refer to the Process
Operations Manual). This forces the HM to do an orderly shutdown and then to fail and
autoboot.
If no US is running, do the following to start up a US with the Operator or Universal
Personality:
1. If it is not already off, turn off the power switch on tower 1 (the right tower) for a
few seconds and then back on. This resets the nodes in that tower, including US
number. 1. Wait for > to appear in the upper left corner of the screen of the monitor
connected to tower 1.
2. On the Operator's Keyboard, press LOAD. N,1,2,3,4,X appears.
3. Press the ALPHA SHIFT key, (until the LED comes on), key in N, then press
ENTER. Several messages appear, ending with OPR, UNP?? (UNP is for
Universal Personality.)
4. Key in OPR or UNP. Press ENTER. If you make a typing mistake, either use
the back arrow key or left tab to recover.
5. Wait a few minutes for the Console Status display to appear. If it doesn't appear
within five minutes, the HM probably did not autoboot, in which case, you should
try to load the system from cartridges. Refer to 5.1.1.2 for the procedure.
Beeping Noise—As the US Operating Personality comes up, you may hear a beeping noise
indicating that some alarm needs to be evaluated and acknowledged. For now you can stop
the noise by pressing the SIL (silence) key.
Enhanced Micro TDC 3000 User's Manual
NOTE
NOTE
5-3
5.1.1
9/95