5 PROTECTION

Icons
Alarm Contents
Over Frequency Stop
Under Frequency Stop
Temp. High
Temp. High Input
Oil Pressure Low Input
Gen Over Current
Gen Over Current
Gen
Over
Cooling Shutdown
Gen Voltage High
Gen Voltage Low
Fail to Crank
Outside
Alarm Input
Fuel Level Low
Fuel Level Low Input
Fail to Stop
Battery Voltage Low
Battery Voltage High
NOTE 1: Shutdown alarms are latched signals and alarms can be removed by using Stop key (in stop status); warning
alarms are not latched.
MGC300 Genset Controller
Table 5 Alarm Types
Type
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Warning
Shutdown
Current
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Warning
Warning
Warning
Warning
Warning
Version 1.1
MGC300 Genset Controller User Manual
Trigger
Gen frequency is above over frequency limit for 2s, it
will issue alarm;
Detected when genset is running normal; gen freq. is
less than under frequency limit for 10s, and it alarms.
Detected after safety on delay; when temp. high is
above high temp. limit for 3s, it will issue alarm;
Detected after safety on delay; when temp. high input is
active, it will issue alarm;
Detected after safety on delay; it alarms when oil
pressure low input is active;
Action is set to Warning; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Action is set to Shutdown; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Action is set to Cooling Shutdown; gen current is over
pre-set value and lasting time is over delay, it alarms;
Detected after safety on delay; gen voltage is over the
threshold, and this lasts for over delay, and it alarms;
Detected after genset running; gen voltage is lower
than threshold for over the delay time, and it alarms;
It alarms when starter doesn't start the engine in the
range of the pre-set start times;
When "outside shutdown alarm" is configured for the
input port, and when the input is active, it alarms;
When fuel level is lower than the threshold for 10s, it
alarms;
When fuel level low input is active, it alarms;
Complete stop time is over but genset still stops
completely and controller will alarm;
Battery voltage is lower than the threshold for 20s, it
alarms;
Battery voltage is higher than the threshold for 20s, it
alarms;