2 PERFORMANCE AND CHARACTERS

——Graphic LCD display (backlight), LED indicators, push-button operation;
——Acrylic material for hard screen protection;
——Wide power supply range DC (8-35)V, which can suits different environments of starter battery
voltages;
——Collect and display mains/gen 3-phase voltage, 3-phase current, frequency, and power
parameters;
Mains
Line voltage
Phase voltage (L1, L2, L3)
Frequency
Load
Current
Total active power P
——Mains has over volt, under volt, over frequency, under frequency, and loss of phase functions;
Gen has over volt, under volt, over frequency, under frequency, over current, over power, and
loss of phase functions;
——Precisely measure all parameter values of engines:
Temperature ° C
Battery voltage V
Speed RPM
——Genset fault protection and display function;
——Controller has 4 working modes: manual, auto, stop, and test mode, and MGC310 has stop,
manual, auto modes, and MGC320 has manual, auto, stop, and test mode;
——Parameter setting function: allows users to change and set the parameters, which won't be lost
on system power off; a majority of parameters can be adjusted from front panel, and all
parameters can be configured by RS485 on PC;
——1 programmable input port, 2 fixed input ports;
——2 fixed relay output ports (fuel output, start output);
——2 programmable relay output ports;
——All parameters are adjusted digitally, improving the whole case's reliability and stability;
——Sealing gasket is designed between the closure and the control window, whose dustproof and
waterproof performance can be reached to IP65;
——Metal fixing clips are used to stable the controller;
——Modular structure design, pluggable wiring terminal, and built-in installation, make it compact in
structure and easy to install.
MGC300 Genset Controller
(L12, L23, L31)
(Hz)
(Ia, Ib, Ic)
Fuel level %
Accumulated running time H (max. 9999 hours)
Accumulated start times (max. 90000000 times, display only on PC software)