Initial Startup - Huawei UPS5000-S-880 kVA User Manual

Table of Contents

Advertisement

UPS5000-S-880 kVA
User Manual (CMI)

5.1.2.1 Initial Startup

Step 1 After the MDU starts properly, set the language, time, network parameters, system
parameters, and battery parameters on the Settings Wizard screen.
Set system parameters with caution because the settings determine normal UPS operation.
Figure 5-1 Settings Wizard
Issue 02 (2020-01-10)
Default User
operator (common user)
browser (browsing user)
Single/Parallel and Output frequency must be correctly set. Otherwise, the UPS running
may be affected.
Output voltage level refers to the line voltage level.
Copyright © Huawei Technologies Co., Ltd.
Preset Password
LCD
WebUI
WebUI
5 Operations
000001
Changeme
N/A
155