Huawei UPS5000-S-880 kVA User Manual page 39

Table of Contents

Advertisement

UPS5000-S-880 kVA
User Manual (CMI)
Functions
The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).
Specifications
Issue 02 (2020-01-10)
Silk Screen
Description
EPO_NC
EPO port
EPO_12V
+12 V
SWITCH
Port for monitoring the UPS
STATUS_OUT
output circuit breaker
SWITCH
Port for signal ground
STATUS_0V
SWITCH
Port for monitoring the
STATUS_MT
maintenance circuit breaker
SWITCH
Port for signal ground
STATUS_0V
SWITCH
Port for monitoring the
STATUS_BP
bypass input circuit breaker
SWITCH
Port for signal ground
STATUS_0V
SPD
Port for monitoring the input
AC surge protective device
(SPD)
0V
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
Hot-swappable
0.5 U high
Copyright © Huawei Technologies Co., Ltd.
Status
is triggered.
If the normally closed
(NC) port is
disconnected from the
EPO_12V port, EPO
is triggered.
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Disconnected:
circuit breaker ON
Connected: circuit
breaker OFF
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected: SPD
enabled
Disconnected:
SPD disabled
2
2
to 1.5 mm
.
2 Overview
Initial Status
Connected
Connected
Disconnected
Connected
Connected
31