UPS5000-S-880 kVA
User Manual (CMI)
Alarm ID
Alarm Name Severity
(Alarm ID-
Alarm
Cause ID)
0032-1
Battery
overvoltage
protection
0036-2
Battery
maintenance
reminder
0037-1
Battery
undervoltage
0040-7
Rectifier
abnormal
0043-1
Fan abnormal
0043-2
Issue 02 (2020-01-10)
Cause
Critical
The battery voltage
is greater than the
upper threshold.
The configured
number of batteries
is less than the
actual number.
The actual number
of batteries does
not meet
requirements.
Warning
The batteries are due
for maintenance.
Critical
The UPS works in
battery mode for a
long time.
Charger fault
Critical
The fans for the
power module are
abnormal.
The air channel of
the power module
is obstructed.
Critical
The fans for the
power module are
abnormal.
The fan monitoring
cable for the power
module is
abnormal.
Fan fault
Copyright © Huawei Technologies Co., Ltd.
Solution
detector is enabled. If yes,
disable it and check whether the
alarm is cleared. If the alarm
persists, the dry contact board
may be faulty. Replace the
board.
1. Check the battery voltage.
2. Check that the configured
number of batteries matches the
actual number.
3. Check that the actual number of
batteries meets requirements.
Maintain the batteries.
1. Check whether the battery
voltage is normal.
2. Check whether the output is
overloaded.
3. Check whether any battery is
damaged. If yes, replace the
battery.
4. Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
1. Check whether the fan is
blocked. If yes, rectify the fault
to restore the normal operation of
the fan.
2. Check whether the fan is
abnormal. Replace the power
module if the fan is faulty.
Replace the faulty power module.
Check the fan or replace the bypass
B Alarm List
192