Item
Maintenance
period (d)
Chg. cur.
Limiting coef
(C10)
Cell float
voltage
(V/Cell)
Cell equalized
chg. volt.
(V/Cell)
Dis. cur. 0.1C
EOD (V/Cell)
Dis. cur. 0.3C
EOD (V/Cell)
Dis. cur. 0.5C
EOD (V/Cell)
Dis. cur. 1.0C
EOD (V/Cell)
Scheduled
shallow
discharge test
Shallow dis.
test dis. ratio
(%)
Issue 02 (2020-01-10)
Description
the time specified by the
maintenance period arrives.
Specifies the interval for
reminding users of battery
maintenance.
Sets a charge current limit. The
limiting coefficient is a multiple
of the battery capacity.
Specifies the battery float
charging voltage.
Specifies the battery equalized
charging voltage.
Specifies the EOD threshold
when the discharging current is
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The UPS records the battery
discharge data as a reference for
battery reserve and lifespan.
Indicates the proportion of the
discharge capacity to the total
discharge capacity.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0–365
0.1C10
0.05C10–
0.15C10
2.25 V/cell
2.23 V/cell–2.30
V/cell
2.35 V/cell
2.30 V/cell–2.40
V/cell
1.80 V/cell
1.8–1.9
1.80 V/cell
1.8–1.9
1.75 V/cell
1.75–1.85
1.60 V/cell
1.6–1.75
Disable
Disable, Enable
20%
10%–50%
113

Advertisement

Table of Contents
loading