UPS5000-S-880 kVA
User Manual (CMI)
Input Settings
Output Settings
Issue 02 (2020-01-10)
Item
Description
time site
one waveform can be stored
waveform
manually.
BCB trips in
If this parameter is set to Enable,
case of EOD
the BCB will trip in case of
EOD.
Item
Description
Input
The value of Input adaptability
adaptability
can be Strong or Weak. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
distortion of the input current
waveform (THDi) is poor, but
the system is stable. Weak input
adaptability is suitable for mains
and AC input sources.
Item
Description
Zero display
If this parameter is set to Enable,
with no load
the output current is displayed as
output
0 when no load is output. The
output load rate is displayed as
3%. When this parameter is set to
Disabled, the output current and
output load rate are not adjusted
to zero.
Calib. output
If this parameter is set to Enable,
current if no
the current at no load will be
load
calibrated once automatically.
This function can be used only
when the UPS carries no load.
Output
Set this parameter based on the
interruption
output interruption time
acceptable to loads.
transfer time
(ms)
Max. BPM
Cross currents occur during the
transfer times
transfer between bypass mode
and normal mode, which impacts
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable, Enable
Default Value
Value Range
Strong
Strong, Weak
Default Value
Value Range
Enable
Disable, Enable
Disable
Disable, Enable
0
0 ms, 40 ms, 60
ms, 80 ms, 100
ms, 120 ms
5
1–10
130