The UPS works in bypass mode under the following circumstances:
If you set the UPS to ECO mode and the bypass voltage is within the specified range, the UPS
works in bypass mode.
If the power module overload times out, the UPS transfers to bypass mode.
If both active and standby ECMs are abnormal, the UPS transfers to bypass mode.
If the system runs abnormally, the UPS transfers to bypass mode.
The UPS is transferred to bypass mode manually.
Specifications

2.3.5 Control Module

2.3.5.1 Overview

In a standard configuration, the control module consists of two ECMs, one dry contact card,
and one monitoring interface card (from left to right). The four cards are hot swappable. One
subrack is reserved above the dry contact card. A backfeed protection card or dry contact
extended card can be inserted into this subrack.
Figure 2-12 Signal panel on the control module
Issue 02 (2020-01-10)
Indicator
Color
Dimensions (H x W x D): 500 mm x 480 mm x 550 mm
Weight: 83 kg
(1) Ground terminal
(5) Indicators for ECM 1
(9) Indicators for ECM 2
(13) RS485 port
Copyright © Huawei Technologies Co., Ltd.
Status
(2) Parallel port 1
(6) Parallel port 2
(10) Dry contact card
(14) Fast Ethernet (FE)
port
Description
bypass, or the CPLD software is
being upgraded.
(3) BSC port
(4) Ready switch
1
on ECM 1
(7) BSC port
(8) Ready switch
2
on ECM 2
(11) Dry
(12) MDU port
contacts
(15) COM2
(16) COM1 port
port