DR5200

3.1 Electrical installation: 2-wire, loop-powered

3.1.1 Compact version

Terminals for electrical installation
Figure 3-1: Terminals for electrical installation
1 Grounding terminal in the housing (if the electrical cable is shielded)
2 Current output -
3 Current output +
4 Location of the external grounding terminal (at the bottom of the converter)
INFORMATION!
Electrical power to the output terminal energizes the device. The output terminal is also used for
HART
communication.
®
CAUTION!
Use the applicable electrical cables with the cable glands.
Make sure that the current is not more than 5 A or that there is 5 A-rated fuse in the
electrical circuit that energizes the device.
Make sure that the polarity of the power supply is correct. If the polarity is incorrect, you will
not cause damage to the device but the device will not operate.
Open the terminal compartment cover
Figure 3-2: How to open the terminal compartment cover
1 Loosen the lock screw with a 2.5 mm Allen wrench.
2 Turn the cover counterclockwise with a strap wrench.
DR5200QS-LM, EDO#6-13-112 - Issue #3

ELECTRICAL CONNECTIONS

www.drexelbrook.com
3
32