If there are parasitic signals, the device will not measure correctly. Parasitic signals are caused
by:
Objects in the tank.
Sharp corners that are perpendicular to the path of the radar beam.
Sudden changes in tank diameter in the path of the radar beam.
Do an Empty Spectrum recording (refer to Operation
Requirements for flange connections
Figure 2-28: Flange connection
Equipment needed:
• Device
• Flange gasket (not supplied)
• Wrench (not supplied)
• Make sure the flange on the nozzle is level.
• Make sure that you use the applicable gasket for the flange dimensions and the process.
• Align the gasket correctly on the flange facing of the nozzle.
• Lower the antenna carefully into the tank.
• Make sure that you point the device in the correct direction. Refer to "Point the device in the
correct direction" in this section.
• Tighten the flange bolts.
i
Refer to local rules and regulations for the correct torque to apply to the bolts.
DR5200QS-LM, EDO#6-13-112 - Issue #3
Operation) to remove parasitic signals with a filter.