2.8.4 Standpipes (stilling wells and bypass chambers)

Use a standpipe if:
• There is highly conductive foam in the tank.
• The liquid is very turbulent or agitated.
• There are too many other objects in the tank.
• The device is measuring a liquid (petro-chemicals) in a tank with a floating roof.
• The device is installed in a horizontal cylindrical tank.
For more data, refer to the Handbook.
Figure 2-30: Installation recommendations for standpipes (stilling wells and bypass chambers)
1 A stilling well solution
2 A bypass chamber solution
3 Air circulation hole
4 Level of the liquid
CAUTION!
You can drill an air circulation hole if the stilling well is in a closed space (a metallic container).
This condition is necessary to obey TLPR standards. For more data, refer to the handbook.