4.3 Quick Setup (Parameters)

Use this procedure to change the tank height, tank type, output function, output range and give
the top and bottom measuring limits. Values and parameters that can be changed are shown
between the « ... » marks in the illustrations that follow. Push the keypad buttons in the correct
sequence:
CAUTION!
Make sure that you do this procedure before you use the device. The settings in this procedure
have an effect on the performance of the device.
Procedure
Screen
DR5200QS-LM, EDO#6-13-112 - Issue #3
Steps
[> > > > ], [ ] and [> > > > ].
[> > > > ], [^ ^ ^ ^ ], [ ], [ ], [> > > > ] and [^ ^ ^ ^ ].
2 × [> > > > ]
[> > > > ] to change the tank height (H).
[> > > > ] to change the position of the cursor.
[ ] to decrease the value or [ ] to
increase the value.
[^ ^ ^ ^ ] to confirm.
[ ] or [ ] for the selection of the
conditions in which the device is used
(Storage, Process, Agitator).
[^ ^ ^ ^ ] to confirm.
www.drexelbrook.com
OPERATION
Description
Default screen.
Enter configuration mode (2.0.0
SUPERVISOR).
Enter the password (the default password is
shown). If it is necessary to change the
password, refer to the handbook.
Push this button to start the quick set-up
procedure.
The distance from the flange face / thread
stop of the tank connection down to the tank
bottom. If the tank has a dish-shaped or
conical bottom, the tank height is measured
to a point on the tank bottom directly below
the antenna.
If the surface of the product is flat, select
"Storage". If the surface of the product is
disturbed, select "Process". If the surface of
the product is agitated with vortexes and
foam, select "Agitator".