Special functions
If a certain reactive power in
Var have to be entered in the first line along with checking the Inductive box. The time 00:00 also has
to be entered in the other lines. It is not necessary to enter the reactive power.
21�2�4 Variable cos (Phi) shift factor over characteristic curve P/Pn
The function allows the Cos (Phi) to be adjusted according to characteristic curve P/Pn.
With a characteristic curve P/Pn, the ratio of the currently generated power (P) to nominal power
(maximum output) (Pn) is determined. A Cos (Phi) is assigned to ratio by a characteristic curve.
The currently generated power (P) is calculated by the Solar-Log™ based on the inverter data. Mea-
suring the power output intended.
The function is also referred to as Phi (P) .
Type of characteristic curve section
Using this menu item a characteristic curve specified by the grid operator can be stored. In principle a
distinction is made here between a 2 point and a 4 point characteristic curve.
2 point characteristic curve
By selecting "2 point characteristic curve" it is possible to define a characteristic curve using 2 points.
Procedure
•
Variable cos (Phi) shift factor over characteristic curve P/Pn
Select
•
Activate
•
Select
2 point characteristic curve
•
Define
the
check for inductive.***
•
SAVE
settings
The characteristic curve displayed changes according to the values entered.
4 point characteristic curve
By selecting "4 point characteristic curve" it is possible to define a characteristic curve using 4 points.
Procedure
•
Variable cos (Phi) shift factor over characteristic curve P/Pn
Select
•
Activate
•
Select
4 point characteristic curve
•
Define
the
check inductive/under-excited.
•
SAVE
settings
The characteristic curve displayed changes according to the values entered.
118
Var
must be supplied for 24 hours, the time 00:00 as well as the value in
Interfaces
characteristic curve points A, B, C and D
Interfaces
characteristic curve points A, B, C and D
from the menu
based on the boxes U/Uc, Q/SAmax and
from the menu
based on the boxes P/Pn, cos (Phi) and
Need help?