11 19-inch module for SysLink system connector

11.1 Structure and function

The 19-inch module for SysLink extends the functional scope of your EduTrainer
You can connect 8 digital 24 V I/Os each with your model (e.g. MPS) using appropriate cables via two
Centronics plugs A and B. A jumper plug enables outputs to be switched off in the event of an EMERGENCY-
STOP.
The plugs A and B are set as follows in the factory:
A: Station (24 V via EMERGENCY-STOP jumper)
B: Operation (24 V continuous)
This setting can be changed via the jumpers JP1 and JP2.
The socket C enables the connection of 4 analogue inputs and 2 analogue outputs.

11.2 Commissioning

1. Connect the digital inputs/outputs to the PLC using a flat cable:
SV3/SV4 and SV7/SV8: Siemens S7 (16-pin)
SV1/SV2 and SV5/SV6: Other controller types (10-pin)
2. If using modules in parallel, these can be connected via the free insulation-displacement connectors
SV1 to SV8 using flat cables.
3. Connect the analogue inputs/outputs to the PLC using a flat cable:
SV12/SV13: Siemens S7 analogue additional module with 20-pin plug (2 x 16-pin)
SV10/SV11: Siemens S7 integrated analogue module with 40-pin plug (2 x 16-pin)
SV14: Other controller types (16-pin)
4. If using modules in parallel, these can be connected via the free insulation-displacement connector
SV14 using flat cables.
5. Connect the 24 V power supply by means of the 3-pin insulation-displacement connector SL1 or SL2.
6. Use the jumpers JP1, JP2, JP5, JP6 and JP7 to define whether the PLC modules are supplied directly via
24 V or via 24 V NA. 24 V NA is switched off in the event of an EMERGENCY-STOP.
(jumper between pins 1 and 2: supply via 24 V NA;
jumper between pins 2 and 3: supply via 24 V).
7. An EMERGENCY-STOP can be realised via the short circuit connector (24 V NA is disconnected).
8. Screw the 19-inch module into the frame.
Note
For all preferred versions EMERGENCY-STOP and bit 1.5 are connected via wire links:
10-pin plug SV6, pin 1
16-pin plug SV8, pin 9
These wire links are required if an MPS station is linked to this module. They must be removed for other
applications of this module.
70
10-pin plug SV1, pin 7
16-pin plug SV3, pin 6
®
PLC system.