Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
16.3. Table Configure basic settings (login = untrained specialist)
Icon BDM/BBS
Icon
Service 1 Settings
Icon Test setup
Icon
Automatic
duration test
Icons for program-
ming the duration
test
Activate/deactivate
test
date
start time
Duration test
time
start time
Duration test
Distance between
tests
Icon Test setup
Icon for automatic
function test
Enter the warning and error thresholds
in % for voltage and temperature.
Already set ex works for EATON
batteries
Allow high charge= The high charge
can be switched off in environmental
conditions such as low air flow or too
high temperatures.
LT Start delay: After the end of the
endurance test the recharging is
delayed.
Quick Check Battery Interruption= For
countries that require shorter inter-
ruption detection times other than EN
50171.
Pub/sub= The transmission of the
battery values to a substation.
Actuate
Date Start time Duration test
Time Start time Duration test
Distance between tests
Actuate
Use the arrow keys to enter the start
time, time and distance between two
tests.