Technical description
Dimensions (W x H x D):
Colour:
Weight:
Assembly:
Degree of protection:
Protection class:
Ambient temperature:
Degree of pollution:
Electromagnetic compatibility:
Rated voltage (Mains):
Rated current (Mains):
Rated voltage (Battery):
Rated current (Battery):
Rated Frequency:
Overvoltage category:
Max. connected load:
Maximum numbers of modules:
Controller ACU DG / HMI:
PSU:
BCM.1:
SKU.1 CG-S:
1x6A
2x3A
4x1,5A
Luminaire circuits:
Charger CM 1,7A
Terminals:
Luminaire circuits
BCM.1
ACU DG
Mains feed
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
1000x600x300 mm
RAL 7035
50 kg
Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 4412
Mounting stability [N]: 2250
IP21
I
-5°C to +35°C
2
Industry EN 61000-6-2, Commercial EN 61000-6-3
UN = 230 V AC
IN = 15 A
216 V DC
IN =12 A
50 or 60 Hz
Mains: III / Battery: II
At +35°C < 3,24 KW
1
1
1
0-4
0-4
0-4
24
1
4 mm² Rigid/flexible
4 mm² Rigid/flexible
2,5mm² Rigid/ 1,5mm² flexible
16 mm² Rigid/flexible
45 DualGuard-S 4C3
Field
A3
A4
A1
B1
B2
B3-4
A2
B3
A2
A2
A1
A3
115