41 DualGuard-S 12C

41 DualGuard-S 12C
The DualGuard-S 12C in IP21 (IP31 optional) version with
individual cable entry in accordance with EN 50171 is sui-
table for supplying up to 48 circuits for safety and escape
sign luminaires 230V / 216V AC/DC in the power range up
to 7 .5KW. A shunting feeder for mains and battery enables
the connection of a sub-station of type DualGuard US,
DualGuard-S ESF30 and DualGuard-S SOU. The wiring
system with rounded mounting fields does without classic
cable ducts and, in combination with the natural ventilation
and the large ventilation slots of the mounted modules,
ensures a homogeneous control cabinet climate which has
been proven by heating tests in accordance with EN 61439-
1 under nominal load conditions. The clear, self-explanatory
internal modular field structure, taking contact protection
into account, rounds off the appearance.
The extensive catalogue of cabinet accessories such as
special locks, door hinges right/left, cable entries, bases in
various heights, IP31 retrofit kits and IP54 on request offers
the right solution for most customer-specific requirements
without long delivery times.
The colour touch display with automatic testing device and
individual luminaire monitoring with individual status and
name indication per luminaire in conjunction with system-
related ECG / LED supply module including monitoring
module without additional data line reports and records the
operating status of the external phase monitor modules,
the insulation monitoring device as well as the battery
strings and, if battery block monitoring technology is used,
the operating status of each individual battery block.
96
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de