35 3-Pm-Io-Inv Module - Eaton CEAG DualGuard-S Mounting And Operating Instructions

Table of Contents

Advertisement

35 3-PM-IO-INV Module

In order to avoid the risk of power failures, it is necessary
to permanently monitor the function of the general lighting
light distributors in order to switch on the safety lighting
in the event of a fault. The CEAG 3-PM-IO-INV modules
are therefore an important part of the safety system. The
safe functioning of the entire system must be constantly
monitored and, in the event of faults, the system must
switch on the safety lighting automatically. The results of
both automatic and manual tests must be logged. At the
same time, emergency luminaires should be switched on
with the general lighting during normal operation. EATON´s
CEAG 3-PM-IO-INV modules offer all these functions in one
device in compliance with standards. Deviating from the
3-PM-IO module, the 3-PM-IO-INV module offers inverted
measuring inputs so that individual circuit breakers can be
monitored with integrated signalling contacts.
The easily accessible test button offers the advantage that
an interruption of the mains voltage is not necessary to
check the function of the voltage monitoring devices. As a
rule, one of the monitored phases must be enabled without
Technical description
Dimensions LxHxT:
Weight:
Installation:
Degree of protection:
Protection class:
Ambient temperature:
Storage temperature:
Relative humidity:
Air pressure:
Electromagnetic compatibility:
Rated voltage Input (Mains):
Switching thresholds:
Rated voltage:
Rated current:
Rated frequency:
Degree of pollution
Overvoltage category Input (Mains):
Overvoltage category 24V supply:
Rated insulation voltage:
Heat dissipation:
RS 485 Bus connection:
Polarity:
Bus Topologie:
KabelType:
Maximum cable lenght:
Terminating resistor:
Terminals Connection cross-sections:
Ordering details
Type
3-PM-IO-INV Module
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
107x90x58 mm³
0,2 kg
DIN Rail Snap on
IP20
II
-10°C...+40°C
-20°C...+65°C
10%....95% no condensation
795....1080 hPa
Industry EN 61000-6-2, Commercial EN 61000-6-3
UN = 220....240 V AC
≤ 60% UN OFF
≥ 85% UN ON
19.2....30 V DC
0,25A
50 or 60 Hz
2
III
II
264 V
< 6.6 W
≤ 30 V SELV
Indipendent
Linie
Z.B. IY(ST)Y 4x2x0,8mm
1200m
120Ω
0.2-2.5 mm² rigid/flexible
Description
Phase monitor / light switch interrogation Bus mo-
dule for DIN rails Mounting with inverted inputs
a test button, which at least leads to a failure of the power
supply of the general lighting and thus to severe disturban-
ces of the operational processes.
IMPORTANT NOTE
Inputs 5 to 8 report a power failure which is forwarded to
the visualization (HMI, WEB, VisionGuard) with the desti-
nation specified in the test book. Inputs 1 to 5 are used to
query the light switch for general lighting and do not signal
a power failure.
Order No.
40071361680
35 3-PM-IO-INV Module
73