17 General product description DualGuard-S

17 General product description DualGuard-S
The DualGuard-S central battery system reliably supplies
safety and escape sign luminaires with power (230V
AC/220 V DC), automatically checks itself and monitors
each of the connected CG-S luminaires (up to 20 per circuit)
simply via the supply line. Thanks to STAR technology, the
switching mode of each connected CG-S luminaire can be
freely programmed via the control section of the central
battery system within a 50 or 60 Hz grid. This means that
mixed operation of maintained light, switched maintained
light and non-maintainedy light is possible in one and the
same circuit - and that without an additional data line! The
colour touch display in 4.3" or 7" version with non-volatile
program memory monitors and controls the central bat-
DualGuard-S 20
DualGuard-S 28
tery system via the ACU DG module. All functions of the
connected devices and emergency lights are automatically
checked and reported.
The DualGuard-S finds all luminaires and I/O modules via
three search icons and automatically detects all modu-
les and luminaires addressed during installation. The
VisionGuard monitoring software can be connected via an
Ethernet interface.
DualGuard-S Typees
Depending on the requirements on site, different system
configurations are used. These standardized configurations
have designations, e.g.:
DualGuard-S 28 or DualGuard-S 20
For operation with max. 28 or 20 circuit modules SKU.1.1
CG-S with 88 circuit. Up to 6 substations can be supplied
DualGuard-S US 30
DualGuard-S US 38
with battery current and mains current (up to 6 substations
1-phase, up to 2 substations 3-phase).
DualGuard-S LAD 100A
The charging and shunting distributor supplies up to fifteen
1-phase or five 3-phase substations with mains and battery
voltage. In addition, up to four circuit modules can supply
and control 16 circuits.
DualGuard-S 12C, DualGuard-S 12C6, DualGuard-S
20C6, DualGuard-S 12C4, DualGuard-S 4C3
for operation with max. 12 or 20 circuit modules SKU.1.1
CG-S.
DualGuard-S 12C
DualGuard-S 12C4
DualGuard-S US 38, US 30, US 23, US 15, US 7
For operation with max. 7 , 15, 23, 30 or 38 circuit modules
SKU.1.1 CG-S. With these substations, the charging techno-
logy of the connected battery emergency power supply is
not required; the battery and mains power supply is provi-
ded via the DualGuard-S system.
DualGuard-S 20C6
DualGuard-S 12C6
48